Premises
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (c) be constructed of material that is suitable for the purpose for which it is to be used and is durable and free of
any noxious constituent;
- (f) have floors, walls and ceilings that are hard and smooth and otherwise constructed in such a way that they can be
cleaned and are impervious to moisture at the locations in the establishment where
- (i) food animals are slaughtered or carcasses are dressed, and
- (ii) meat products are refrigerated, stored in a refrigerated state, processed, packaged, labelled,
shipped, received or otherwise transported;
- (8) The walls, ceilings, floors, doors, windows and other parts of any area of a registered establishment where food animals are slaughtered,
carcasses are dressed or meat products are refrigerated, frozen, stored, processed, packaged, labelled, shipped, received or otherwise handled shall
not be composed of any material, or have applied to them any coating, other than a material or coating that is durable and does not contain any
noxious constituent.
- If the Director suspects that a material or coating referred to in subsection 34(8) or a chemical agent referred to in subsections 34(11) and
(11.1) may be a health hazard, the Director shall prohibit its use in a registered establishment unless it has been
- (a) evaluated by the Director and found suitable for use in the establishment; and
- (b) registered by the Director in a register kept for that purpose.
Ensuing Policy Requirements
Walls, Ceilings and Overhead Structures, Floors, Doorways and Doors, Windows, Elevators, Shafts, Stairs
To promote sanitary conditions in a registered establishment, it is essential that walls, ceilings and overhead structures, floors, doorways and
doors, windows, elevators, shafts, stairs be constructed of smooth, hard and impervious material, and be free of pitting, indentations, cracks and
crevices.
Walls
Design and construction of the wall to floor, inside wall-to-wall, and wall to ceiling corners must allow for easy cleaning and inspection and
prevent accumulation of contaminants.
The design and construction of ledges of wall concrete curbs, horizontal wall structural steel support or windows sills, where required, shall
prevent the accumulation of contaminants or possibilities of storing any objects on the ledges.
Ceilings and Overhead Structures
Design and construction of ceilings and all overhead structures must prevent the potential contamination of meat products and allow for easy
cleaning and inspection.
Ceiling height and location of overhead structures must provide adequate clearance for cleaning and inspection of equipment, promote adequate
ventilation and air movement, and facilitate the easy movement of product, equipment, etc. throughout the registered
establishment.
Rails and Rail Support Systems
Rails and rail support systems shall be designed, constructed, and installed to promote sanitary conditions.
Rail heights, spacing and locations shall be appropriate to prevent suspended meat products from potential sources of contamination.
Rail heights, spacing and locations shall meet specific program requirements.
Floors
Floors shall be designed and constructed to promote the effective cleaning, removal of all wastes and prevention of potential contamination of
meat products.
Doorways and Doors
Doorways must be of sufficient size to facilitate the movement of product, equipment, and personnel, and to prevent the potential contamination of
meat products.
The doorways and doors shall be designed and constructed to provide for proper protection against the entry of potential contaminants for meat
products.
All doors located in rooms/areas intended for handling of meat product, ingredients and packaging materials shall not lead directly to the
outside, except for the doors located in shipping/receiving areas and intended for shipping and receiving activities, and doors designated as
emergency exits where required by applicable legislation.
Windows
Windows shall be designed and constructed to provide for proper protection against the entry of potential contaminants for meat products.
Windows shall be designed and constructed of materials that are of a type that will not cause contamination of meat products in the event of
breakage.
Elevators, Shafts, Stairs
Elevator cars and shafts intended for the transportation of meat products shall be designed, constructed and installed to promote sanitary
conditions, and made of materials meeting the same criteria as materials used for the construction of any meat products handling areas.
Stairs, catwalks, walkovers, mezzanines, etc. shall be designed, constructed and installed to prevent potential
direct or indirect contamination of meat products, and made of suitable materials.
Non-mandatory Items for Consideration
None
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (n) subject to subsection (2), be capable of supplying potable hot and cold water that is protected against
contamination and is adequate in quantity and pressure to serve the water needs of the establishment;
- (2) An establishment registered pursuant to subsection 27(3) may supply water other than potable water referred to in
paragraph (1)(n) where it is used solely for fire protection, boilers or auxiliary services and there is no connection between the system for that
water and the system for potable water.
- (11) Every detergent, sanitizer or other chemical agent used in a registered establishment shall be properly labelled
and stored and used in a manner that prevents contamination of meat products, ingredients, packaging and labelling material and of the surfaces with
which they come into contact.
- (12) Where steam is used in the processing of a meat product in a registered establishment, the steam shall be generated
from potable water and shall contain no harmful substances and the supply of steam shall be adequate in quantity and pressure to serve all the needs
of the establishment.
- If the Director suspects that a material or coating referred to in subsection 34(8) or a chemical agent referred to in
subsections 34(11) and (11.1) may be a health hazard, the Director shall prohibit its use in a registered establishment unless it has been
- (a) evaluated by the Director and found suitable for use in the establishment; and
- (b) registered by the Director in a register kept for that purpose.
- Every operator shall carry out control programs in accordance with the FSEP Manual and the Manual of Procedures to ensure that
- (c) the requirements of the Act and these Regulations are met in respect of the registered establishment, equipment,
food animals, meat products, ingredients, food additives, chemical agents, packaging and labelling materials, training and any other requirement of a
control program set out in the FSEP Manual and the Manual of Procedures;
Ensuing Policy Requirements
Potable water lines shall be protected from contamination.
Where non-potable water is used, the line(s) shall be clearly and distinctly identified.
Adequate facilities shall be provided for monitoring and maintaining potability, storage, temperature, and distribution of water in registered
establishment. Only potable water shall be used in meat product handling, processing, and sanitation procedures.
Water supplied to a registered establishment shall meet the current limits for potability of Health Canada Guidelines for Canadian Drinking Water
Quality.
Where the supply of potable water is derived from a private well, adequate protection must be afforded to the wellhead to prevent contamination of
the water supply.
Where storage tanks are used, they shall be designed, constructed, and installed in such a way as to prevent contamination of stored water.
Where a registered establishment is supplied with only municipal water, potability analyses of water are required on a semi-annual basis with
satisfactory results.
In establishments supplementing municipal supplies with water from private wells or storage tanks, or using water solely from private wells or
storage tanks, potability analyses of water are required on a monthly basis with satisfactory results.
Samples of water shall be collected from different outlet(s) for each test. This procedure will ensure that the establishment's water
distribution system functions properly and is not a potential source of water contamination.
Where water filters are used, they shall be kept effective and maintained in a sanitary manner.
Water Reuse
The need to conserve water through reuse is crucial given the finite nature of this resource and increasing demands for its use in domestic,
agricultural, and manufacturing activities.
Water re-circulated for reuse should be treated and maintained in such a condition that no risk to the safety and suitability of meat products
results from its use.
Proper maintenance of water conditioning systems is critical to avoid the systems becoming sources of contamination. For example, filter systems
can become sources of bacteria and their metabolites if bacteria are allowed to grow on the organic materials that have accumulated on the
filter.
Appropriate safety and suitability criteria that meet the intended outcomes should be established for any water used in the registered
establishment.
These criteria depend upon the origin and the intended use of the water. For example, reuse water intended for incorporation into a meat product
shall meet the microbiological specifications for potable water.
Water reuse or recycling may be allowed in a registered establishment under certain conditions identified by the specific program
requirements.
Reconditioning of water for reuse and use of reclaimed, re-circulated and recycled water should be managed in accordance with HACCP principles. Any reuse of water should be subject to a hazard analysis including
assessment of whether it is appropriate for reconditioning. Critical control point(s) should be identified, as appropriate, and critical limit(s)
established and monitored to verify compliance.
Water Treatment
Where water treatment systems are used in a registered establishment (e.g., chlorination, ozonation, etc.) it is essential that the operator establish procedures to ensure the treated water is potable.
It is required that a metering device for adding water treatment agent in the correct concentration, relative to the water flow rate, is designed
to readily indicate malfunction.
The operator shall establish the necessary frequency of tests of treated water to be performed in a registered establishment to determine the
level of a water treating agent at a specific point in the water supply system which is remotely located from the agent application site, but before
distribution of water to the establishment system.
The operator shall establish the maximum use level of ozone in the water system before the Health Canada residual level of 0.05 ppm of ozone is reached in the atmosphere within the registered establishment.
For information concerning the use of hyper-chlorinated water in a registered establishment, please refer to specific program requirements
indicated in the applicable chapter(s) of the Meat Hygiene Manual of Procedures.
Ice
The operator shall ensure that the ice used in the registered establishment is manufactured from potable water only.
The operator shall conduct the ice potability test on a regular basis. The frequency of ice potability testing shall take under the consideration
the source of ice being used in the registered establishment (i.e., manufactured on site or purchased from the
outside sources).
Steam
Only those boiler treatment agents, which are listed in the Reference Listing of Accepted
Construction Materials, Packaging Materials, and Non-Food Chemical Products may be received and used in a registered establishment.
Boiler treatment agents shall be used according to the manufacturers directions and do not lead to the contamination of meat products.
Non-mandatory Items for Consideration
None
Meat Inspection Regulations, 1990 Requirements:
- (3) In addition to the requirements set out in subsection (1), every registered establishment in which food animals are
slaughtered shall:
- (e) have adequate facilities for the cleaning of protective clothing and a sufficient number of directly drained hand
washing facilities that are remote controlled or timed; and
- (5) In addition to the requirements set out in subsection (1), every registered establishment in which meat products are
processed, packaged or labelled shall have:
- (b) a sufficient number of directly drained handwashing facilities that are remote controlled or timed; and
- (6) In addition to the requirements set out in subsection (1), every registered establishment in which meat products are
refrigerated, frozen or stored in a refrigerated or frozen condition and in which imported or detained meat products are inspected shall have:
- (a) directly drained handwashing facilities that are remote controlled or timed, in all rooms where imported or detained
meat products are inspected or prepared for inspection; and
Ensuing Policy Requirements
Hand wash facilities shall be:
- operated in a hands-free manner;
- capable of supplying hot and cold water in an appropriate amount under sufficient pressure; and
- easily accessible for production and inspection personnel
The location of hand wash facilities shall meet specific program requirements.
For operational requirements of hand washing facilities refer to section 3.9.2 of
this chapter.
Non-mandatory Items for Consideration
None
3.4.4 Drinking Water Fountains
Meat Inspection Regulations, 1990 Requirements:
- (1.1) The building, equipment, utensils, transport containers and all other facilities of a registered establishment shall be maintained in a
sanitary condition.
- (5) Every person who enters or is in any area of a registered establishment where a meat product or an ingredient is prepared, packaged,
labelled, stored or otherwise handled shall refrain from spitting, chewing gum, smoking or consuming tobacco products or consuming food, other than
water dispensed from a drinking fountain
Ensuing Policy Requirements
Drinking water fountains, where provided, must operate in a hands-free manner, be directly drained, easily accessible and protected from
contamination.
Non-mandatory Items for Consideration
None
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (u) have, where utensils are used in the handling of a meat product, water sanitizers that are capable of being
maintained at a temperature of not less than 82°C for the sanitizing of the utensils;
Ensuing Policy Requirements
Water sanitizers shall be capable of maintaining visibly clean water during operation.
For operational requirements of water sanitizers, refer to section 3.9.2 of this
chapter.
Non-mandatory Items for Consideration
None
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (s) have adequate facilities and means for the thorough washing, cleaning and sanitizing of equipment;
Ensuing Policy Requirements
An adequate number of conveniently located facilities must be provided throughout the registered establishment for the cleaning of rooms,
equipment, and protective clothing.
These facilities shall not create any potential source of contamination to food.
Where required, temperature indicators shall be installed at facilities supplying water at the temperature of 82°C or higher.
Non-mandatory Items for Consideration
None
3.4.7 Drainage and Sewage System
3.4.7.1 Drains
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (p) have drainage and sewage systems that are
- (i) designed, constructed and maintained in accordance with the plumbing code of the province in
which the establishment is located,
- (ii) adequate to handle all waste,
- (iii) equipped with traps and vents,
- (iv) designed and constructed so that there is segregation of the effluent of human waste and other
waste, and
- (v) located in such a manner as to prevent contamination of food;
- (9) All lavatories, sinks and drains in a registered establishment shall be maintained in a manner that prevents any odours or fumes there from
pervading any room where meat products are refrigerated, stored, processed, packaged, labelled or otherwise handled.
Ensuing Policy Requirements
Every means of establishment effluent disposal must meet all municipal and provincial requirements.
The design and construction of drainage and sewage systems shall not pose the risk of contaminating meat products.
The drainage from toilets, urinals, floor drains, and hand wash facilities in welfare areas shall be separate and apart from other sewage lines to
a point outside of the establishment.
Adequate drainage must be present throughout the registered establishment, where required, and must comply with the provincial plumbing code in
which the establishment is located. The number, size, and location of drains and drain inlets shall provide proper and constant removal of the fluid
wastes and prevent water from flooding the surrounding areas or pooling around the drain inlet. All floor and hub drains must be deep-seal trapped
and all drain lines must be properly vented to the outside air and equipped with effective rodent screens.
Non-mandatory Items for Consideration
None
3.4.7.2 Separation of Organic Matter from Establishment Effluent
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (k) where equipped with a catch basin, grease trap or interceptor for the purpose of separating solid matter from
effluent, have those structures located in the inedible products area;
Ensuing Policy Requirements
All means of separating organic matter from the plant effluent (e.g., catch basins, grease traps, interceptors)
where required by local authorities, shall be located either in:
- the inedible products area; or
- a dedicated room of the registered establishment with outside access only; or
- outside of the establishment.
The area surrounding an outside separator shall have an impervious surface and shall be sloped towards the separator.
Non-mandatory Items for Consideration
None
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (g) have rooms and areas with adequate lighting, ventilation and plumbing to meet the requirements of the activities
carried out therein and constructed so as to facilitate their cleaning and disinfection;
- (h) be equipped, in areas where food, food additives or packaging materials are exposed, with light bulbs and fixtures
that are of a type that will not cause food contamination in the event of breakage;
Ensuing Policy Requirements
All rooms and areas of the establishment must be properly lighted by natural light, artificial light, or both. Special attention must be given to
the amount and direction of lighting in inspection areas to prevent glare while providing the required maximum illumination.
All light in meat product inspection areas shall be without shadow or glare and have a minimum colour rendering index value of 85 so as not to
distort the normal colour of meat products.
Specifically:
- all CFIA inspection stations and operator inspection sites
(e.g., head preparation, check trim station, boneless meat reinspection site, return and imported meat reinspection
sites, etc.) measured at the lowest inspection point shall be 540 lux;
- MPIP poultry carcass inspection stations and carcass
salvage station(s) on the kill floor measured at the carcass abdominal cavity level shall be 2000 lux;
- inspection stations in high line speed beef or hog slaughter measured at the lowest carcass, head, viscera and abdominal
cavity levels shall be 1000 lux;
- all suspect pens or areas designated for CFIA ante mortem
inspection measured at lowest inspection point shall be 540 lux. This may be reduced to 110 lux after CFIA inspection;
- all workrooms (i.e., slaughter floor, processing and packaging areas [edible and
inedible meat products]) measured at the lowest working surface level shall be 220 lux; and
- Light sources and fixtures must not be a potential source of contamination to meat products. In this regard, design and
location are important considerations.
Non-mandatory Items for Consideration
Refer to to the following links for information on energy efficiency and Colour Rendering Index (CRI) ratings:
- Colour rendering index (CRI) General Service Lamps
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (g) have rooms and areas with adequate lighting, ventilation and plumbing to meet the requirements of the activities
carried out therein and constructed so as to facilitate their cleaning and disinfection;
- (m) have lavatories and, where appropriate, dressing rooms and lunch rooms that are
- (iii) well lit and ventilated, and
- The temperature and humidity of every room in a registered establishment where a meat product is refrigerated, stored,
processed, packaged, labelled, shipped, received or otherwise handled shall be controlled to prevent the formation of moisture on walls, ceilings or
equipment.
- Every holding pen that is used for food animals awaiting slaughter shall be provided with adequate ventilation and shall
not be used in a manner that results in their overcrowding.
Ensuing Policy Requirements
Proper location of air intakes and the use of effective filters are essential to prevent the introduction of air contaminated with insects, dust,
smoke, objectionable odour, etc.
Airflow must move from microbiologically sensitive areas towards the less sensitive areas.
Non-mandatory Items for Consideration
None
3.4.10 Room/Area Temperature and Humidity
Meat Inspection Regulations, 1990 Requirements:
- (1) It is a requirement for the registration of an establishment pursuant to subsection 27(3) that the establishment
- (v) have adequate means of establishing, maintaining and verifying the temperature and humidity of
rooms and areas where meat products are refrigerated, frozen, stored, processed, packaged or labelled; and
- Where a low temperature is required for the preservation of a meat product, the temperature in a room or area of a registered establishment in
which that meat product is processed, packaged, labelled or handled shall not exceed 10°C.
Ensuing Policy Requirements
Applicant/operator shall consult with appropriate chapters of the Meat Hygiene Manual of Procedures for Specific Program Requirements.
Non-mandatory Items for Consideration
None
3.4.11 Repealed
Content moved to section 3.4.1 of this document.
3.4.12 Check Trim Station
Meat Inspection Regulations, 1990 Requirements:
- No meat product and no substance used in the processing, packaging, labelling or handling of a meat product in a
registered establishment shall be contaminated.
- Every operator shall carry out control programs in accordance with the FSEP Manual and the Manual of Procedures to ensure that
- (c) the requirements of the Act and these Regulations are met in respect of the registered establishment, equipment,
food animals, meat products, ingredients, food additives, chemical agents, packaging and labelling materials, training and any other requirement of a
control program set out in the FSEP Manual and the Manual of Procedures; and
Ensuing Policy Requirements
Where check trim station(s) is(are) required by specific program requirements the operator shall refer to Chapter 4, Chapter 17 and Chapter 19 for information concerning the locations of check trim stations within the
registered establishment.
Check trim stations shall be equipped with:
- adequate lighting as prescribed in section 3.4.8;
- hand washing facilities as prescribed in section 3.4.3;
- water sanitizer for utensils as prescribed in section 3.4.5; and
- containers for holding inedible trimmings.
The design, construction and installation of check trim station shall not create any source of potential contamination, and be effective for the
purpose.
Non-mandatory Items for Consideration
None
Next page: Section 3.5 | Previous page:
Section 3.3