Drawings Review Checklist for Plant Pest Containment Facilities
Facility:
Rooms:
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Containment barrier outlined and appropriate | ||||
| 2. Office area located outside of laboratory | ||||
| 3. Entry and exit is to be via an anteroom. | ||||
| 4. Insect traps to be provided in the anteroom of the containment zone. | ||||
| 5. Clean/Dirty change area separated by a walk-through shower (if required) | ||||
| 6. Double door pass-through autoclave with interlocking doors or visual/audible alarm (if required) | ||||
| 7. Tight-fitting doors to be provided to deter ingress or egress of arthropods. | ||||
| 8. Large door to allow entry of equipment | ||||
| 9. Interlocking door system (with manual override) or SOPs | ||||
| 10. Decontamination ports (optional) | ||||
| 11. Airlock area for gaseous decontamination (optional) | ||||
| 12.Dunk tank (optional) | ||||
| 13. Pass through (optional) |
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Able to withstand disinfectants | ||||
| 2. Continuous (can have welded seams) | ||||
| 3. Seal maintained between floor and walls (cove floor finish 15 cm up the wall is recommended) | ||||
| 4. Floor slip resistant |
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Containment zone to be screened or sealed for PPC-1 and PPC-2, and sealed for PPC-3 and PPC-2 arthropod containment zones. | ||||
| 2. All penetrations are sealed or screened at the containment perimeter (verify the specification for product detail) -Water plumbing -Gas, etc. |
||||
| 3. Windows (if present) to be sealed or screened and provide the proper level of security |
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Pressure monitoring devices provided at the laboratory zone entrance to monitor negative pressure between containment zones. | ||||
| 2. Pressure point reference (to what?; corridor, clean change area) | ||||
| 3. Room static pressure monitoring lines provided with filters of at least equal efficiency to HEPA filter. | ||||
| 4. Alarm to be provided inside/outside the laboratory to signal air handling systems failure |
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Separate from other areas of lower containment or, if combined with areas of lower containment provided with a bubble tight damper or HEPA filter after the connection (e.g. downstream from the connection) | ||||
| 2. Equipped with motorized bubble tight damper or HEPA filter for backdraft protection | ||||
| 3. Equipped with bubble tight dampers to permit gaseous decontamination – can be same bubble tight dampers as required for backdraft protection and for isolation of HEPA filters | ||||
| 4. Bubble tight damper and HEPA filter to be located close to containment barrier | ||||
| 5. Supply ducts located at least 1.5m from BSC or equipped with diffusers | ||||
| 6. Location of supply does not interfere with inward directional airflow | ||||
| 7. Interlocked with exhaust to prevent positive pressurization | ||||
| 8. Ductwork between the room perimeter and bubble tight damper sealed with Class A (SMACNA) | ||||
| 9. Air flow control device and duct sensor located upstream of the supply bubble tight damper or HEPA filter |
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Separate from other areas of lower containment or, if combined with areas of lower containment provided with a bubble tight damper or HEPA filter before the connection (e.g. upstream from the connection) | ||||
| 2. HEPA filtered | ||||
| 3. Equipped with bubble tight dampers to permit gaseous decontamination – can be same bubble tight dampers as required for backdraft protection and for isolation of HEPA filters | ||||
| 4. Bubble tight damper and HEPA filter to be located as close to containment barrier | ||||
| 5. Exhaust ducts located at least 1.5m from BSC or equipped with diffusers | ||||
| 6. Interlocked with supply to prevent positive pressurization | ||||
| 7. Ductwork between the room perimeter and bubble tight damper sealed with Class A (SMACNA) | ||||
| 8. Air flow control device and duct sensor located downstream of the bubble tight damper or HEPA filter |
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Communication system between containment area and outside support area | ||||
| 2. Water supply control located outside of containment | ||||
| 3. Hands-free hand washing sink located at point of exit | ||||
| 4. Emergency eyewash facility in accordance with applicable regulations | ||||
| 5. Emergency shower (if applicable) | ||||
| 6. Drainage traps required to be deep seal depth in considerations of air pressure differentials (15 cm P-traps are recommended) | ||||
| 7. Dedicated drainage systems | ||||
| 8. Drains connected to validated treatment system must be sloped towards sterilization system to ensure gravity flow; consideration should be given to the installation of valves to isolate sections for decontamination; piping to be heat and chemical resistant consistent with application; joints should be by thermo/chemical fusible means or welding to ensure integrity of entire system | ||||
| 9. Plumbing vent lines (including effluent sterilization system) to be appropriately screened or filtered to prevent ingress and egress of arthropods. | ||||
| 10. Plumbing vent lines to be independent of lower containment plumbing lines or to be provided with HEPA filters when connected with laboratories of lower containment | ||||
| 11. Plumbing vent lines to be heat resistant | ||||
| 12. Power circuit breaker outside containment | ||||
| 13. Autoclave condensate drain located on dirty side (or clean side, when provided with a closed connection) | ||||
| 14. Autoclave to be equipped with a cycle log recorder (to record time, temperature and pressure) | ||||
| 15. Critical equipment supported by the emergency generator | ||||
| 16. Emergency lighting to be provided |
| Items to Consider | Yes | No | N/A | Plan # |
|---|---|---|---|---|
| 1. Provided with a bubble tight damper for isolation on the air inlet and outlets | ||||
| 2. Provided with fumigation ports upstream and downstream | ||||
| 3. Provided with upstream injection port and downstream access port for scanning purposes | ||||
| 4. Leak tight |